cover of episode One Family Dwelling Calculation - Submitted Question

One Family Dwelling Calculation - Submitted Question

2019/2/16
logo of podcast Master The NEC - PODCAST

Master The NEC - PODCAST

Shownotes Transcript

Todays Podcast is about a calculation question sent to me by a fella who wanted help on a single family dwelling calculation question he got our of an exam prep book. The question was poorly written but we answered it anyway.Here was the question:62.) Given: A one-family dwelling as follows:-Size: 1,050 square feet of living space, Service: 120/240 volt single-phase, Cooling: 1/3rd HP 120V cooler motor (air conditioning only), Heating: One 1/6 HP 120V furnace blower motor (heating only)-Laundry: One clothes washer-One 5 kW 240V clothes dryer-Kitchen: One 9,5kW range-One 1.9 kVA 120V dishwasher (1/3 HP motor)-One 9 amp 120 V disposalDo NOT use the "Optional" method.Each ungrounded conductor in the service for the single-family dwelling has a minimum net computed load of ____.a) 89 Amps b) 91 Amps c) 95 Amps d) 100 AmpsNow we know the minimum size service for a single family dwelling is 100A but that is not what the question asked.Become a supporter of this podcast: https://www.spreaker.com/podcast/master-the-nec-podcast--1083733/support).